Electrical conduit plays a vital role in protecting electrical wiring from damage, ensuring the safe and reliable operation of electrical systems. Whether in residential, commercial, or industrial applications, electrical conduit safeguards wiring from physical harm, moisture, fire, and other environmental hazards. One of the most important standards governing the use and installation of electrical conduit in Australia and New Zealand is AS/NZS 2053. This standard provides detailed guidelines on the types, materials, and installation practices for various conduit systems, ensuring they meet the necessary safety and performance criteria.
In this comprehensive guide, we will dive into three main AS/NZS 2053 standards:
AS/NZS 2053.2–Conduits and fittings for electrical installations–Rigid plain conduits of insulating material.
AS/NZS 2053.6–Conduits and fittings for electrical installations–Profile-wall smooth-bore conduits and fittings of insulating material.
AS/NZS2053.5 – Conduits and fittings for electrical installations Part 5 corrugated conduits and fittings of insulating material
We will break down their scope, key provisions, and how it applies to different types of electrical conduit, including rigid PVC conduit, flexible PVC conduit, and corrugated conduit. Understanding this standard is crucial for electricians, contractors, and engineers who design, install, or maintain electrical systems in these regions.
By reading this article, you will gain valuable insights into the following:
- The scope of the AS/NZS 2053 standard and its relevance to various types of conduit systems.
- The different types of electrical conduit covered under the standard, such as rigid PVC conduit, PVC conduit, flexible PVC conduit, and corrugated conduit.
- The testing procedures that conduit materials must undergo to meet the required standards for safety and performance.
- The application of AS/NZS 2053 in different electrical installations and environments.
- The importance of compliance with the AS/NZS 2053 code to ensure safe and durable electrical systems.
Note: All content in this article is based on the AS/NZS 2053 2001 version and is owned by Standards Australia.
Understanding Standards Australia
The Role of Standards Australia in Electrical Conduit Regulations
Standards Australia is the national standards organization that develops and publishes standards across a wide range of industries in Australia. It plays a critical role in ensuring the safety, quality, and performance of products and services, including electrical systems. By establishing and updating industry standards, Standards Australia ensures that electrical installations meet the highest levels of safety and reliability, reducing the risk of electrical hazards.
The AS/NZS 2053 standard is a result of the collaborative efforts between Standards Australia and Standards New Zealand. It is part of a broader set of guidelines designed to provide uniformity and consistency in the installation of electrical systems across both countries. AS/NZS 2053 is not only essential for Australian electricians and engineers but also serves as a key reference for electrical installations in New Zealand. The standard applies to various types of electrical conduit, providing guidelines for their construction, installation, and testing to ensure that they meet safety and performance requirements.
The development of electrical standards, such as AS/NZS 2053, aligns with international best practices, while also addressing the unique needs and conditions of the Australian and New Zealand markets. Adherence to these standards is essential for achieving compliance with national building codes and regulations, thus ensuring the protection of both electrical systems and individuals working with them.
The Scope of AS/NZS 2053
The AS/NZS 2053 standard provides comprehensive guidelines for electrical conduit systems, both metallic and non-metallic conduits and fittings, ensuring that they meet safety, durability, and performance requirements. The scope of the standard covers various aspects of conduit systems, including materials, installation practices, and testing procedures. Its primary goal is to protect electrical wiring from external factors such as physical damage, moisture, fire, and chemical exposure.
Conduit Types Defined in AS/NZS 2053
1. AS/NZS 2053.2 – Rigid Plain Conduits of Insulating Material
This section focuses on rigid plain conduits designed to provide robust protection for electrical wiring in fixed installations.
Conduit Types Covered:
Conduíte rígido de PVC: A widely used material due to its lightweight, corrosion resistance, flame retardation, and ease of installation. These conduits are suitable for exposed, embedded, or underground wiring systems.
Non-Flame Propagating Conduits: Specialized conduits designed to minimize flame spread in case of fire, enhancing overall safety in installations.
Aplicações:
Wall and ceiling installations in residential and commercial buildings.
Underground cable protection in infrastructure projects.
Exposed installations requiring UV-resistant and weatherproof solutions.
2. AS/NZS 2053.5 – Corrugated Conduits and Fittings of Insulating Material
This part of the standard defines fully corrugated conduits, which are lightweight, highly flexible, and ideal for dynamic installations requiring adaptability.
Conduit Types Covered:
PVC Corrugated Conduit: Widely used for its adaptability, these conduits are perfect for installations in tight spaces or areas with frequent movement.
UV-Stabilized Corrugated Conduits: Designed for outdoor use, these conduits resist UV radiation and extreme weather conditions.
Aplicações:
Electrical wiring installations in tight or confined spaces.
Dynamic systems subject to frequent movement, such as robotics or machinery.
Outdoor installations requiring resistance to environmental stressors.
3. AS/NZS 2053.6 – Profile-Wall Smooth-Bore Conduits and Fittings of Insulating Material
This type of conduit features a corrugated outer wall for flexibility and strength, with a smooth internal bore to facilitate easy cable pulling. These conduits are ideal for installations requiring a combination of adaptability and durability.
Conduit Types Covered such as:
Profile-Wall PVC Conduits: Featuring a corrugated exterior for enhanced flexibility and strength, paired with a smooth inner surface for easy cable pulling.
Aplicações:
Underground cable routing in utility networks.
Flexible installations requiring smooth interior walls to minimize cable friction.
Infrastructure projects in chemically aggressive environments.
Key Areas Covered by AS/NZS 2053:
AS/NZS 2053 is primarily relevant to the following countries:
Australia: The standard is widely recognized and adopted across the country, forming the basis of many local electrical regulations and compliance requirements.
New Zealand: The standard is also recognized in New Zealand, aligning the two countries’ practices and ensuring that electrical installations meet similar safety and performance standards.
The Main Content of AS/NZS 2053
The AS/NZS 2053 series is a cornerstone of electrical conduit standards in Australia and New Zealand, offering comprehensive guidance on the design, construction, and performance of conduits and fittings for electrical installations. These standards ensure safety, reliability, and compatibility across diverse applications. In this section, we’ll summarize the main aspects covered by the three key standards introduced earlier: AS/NZS 2053.2, AS/NZS 2053.6, and AS/NZS 2053.5.
1. AS/NZS 2053.2 – Rigid Plain Conduits of Insulating Material
This standard provides detailed specifications for rigid plain conduits used in electrical installations. It outlines:
Material Requirements: Standards for insulating materials like PVC, ensuring durability, electrical safety, and resistance to environmental factors.
Dimensões: Specifications of rigid conduits’ diameters and lengths.
Mechanical Properties: Specifications for strength, compression, and impact resistance to meet different duty classifications.
Performance Testing: Criteria for evaluating fire resistance, electrical insulation, and UV stability.
2. AS/NZS 2053.5 – Corrugated Conduits and Fittings of Insulating Material
This part of the series addresses the unique characteristics of corrugated conduits, highlighting:
Design Specifications: The ribbed structure for enhanced flexibility and lightweight construction.
Dimensões: Specifications of rigid conduits’ diameters and lengths.
Material Requirements: Insulating materials like PVC, tailored for high flexibility and durability.
Mechanical Properties: Criteria for resistance to impact, compression, and dynamic movements.
3. AS/NZS 2053.6 – Profile-Wall Smooth-Bore Conduits and Fittings
This standard focuses on conduits with an externally profiled wall and a smooth internal bore. It includes:
Material Standards: Insulating materials suitable for flexible, lightweight conduits.
Dimensional Requirements: Specifications for wall profiles and bore smoothness to facilitate easy cable pulling.
Mechanical and Thermal Properties: Standards for flexibility, impact resistance, and thermal stability.
Detailed Introduction to AS/NZS 2053
AS/NZS 2053.2 – Rigid Plain Conduits and Fittings
AS/NZS 2053.2 is a vital standard in the AS/NZS 2053 series, specifying requirements for rigid plain non-threadable conduits and fittings made of insulating material. These conduits are used primarily to protect cables in electrical installations, ensuring mechanical protection and electrical safety. This section provides a detailed exploration of the standard, its classifications, dimensions, mechanical properties, and the associated testing procedures.
Scope and General Overview
AS/NZS 2053.2 applies to:
Rigid Plain Conduits: Non-threadable, made of insulating materials such as PVC.
Acessórios: Accessories like couplings, elbows, and adaptors designed for use with these conduits.
Classification
Classified by mechanical properties:
- Vert light duty rigid conduit
- Light duty rigid conduit
- Medium duty rigid conduit
- Heavy duty rigid conduit
- Very heavy duty rigid conduit
Classified by electrical characteristics:
- With electrical insulating characteristics
Dimensional Requirements
The standard defines precise dimensional requirements to ensure compatibility and uniformity across installations.
Dimensions of Circular Conduit (Size Chart)
Nominal Size | Outside diameter | Wall thickness | ||||||||
Mean diameter | Very light duty | Light duty | Medium duty | Heavy duty | ||||||
Min. | Max. | Min. | Max. | Min. | Max. | Min. | Max. | Min. | Max. | |
16 | 15.7 | 16.0 | / | / | / | / | 1.6 | 1.9 | / | / |
20 | 19.7 | 20.0 | / | / | / | / | 1.8 | 2.1 | 2.3 | 2.6 |
25 | 24.7 | 25.0 | / | / | / | / | 1.8 | 2.1 | 2.5 | 2.8 |
32 | 31.7 | 32.0 | / | / | / | / | 2.1 | 2.4 | 2.7 | 3.0 |
40 | 39.7 | 40.0 | / | / | / | / | 2.4 | 2.7 | 3.1 | 3.4 |
50 | 49.7 | 50.0 | / | / | / | / | 2.8 | 3.1 | 3.4 | 3.9 |
63 | 62.7 | 63.0 | / | / | / | / | 3.0 | 3.5 | 3.9 | 4.5 |
65 | 75.2 | 75.5 | / | / | / | / | 3.0 | 3.5 | 3.9 | 4.5 |
80 (NZ) | 82.3 | 82.7 | / | / | 2.2 | 2.6 | 3.2 | 3.7 | 4.2 | 4.9 |
80 (AU) | 88.7 | 89.1 | 1.8 | 2.2 | 2.4 | 2.8 | 3.5 | 4.1 | 4.6 | 5.3 |
100(NZ) | 110.0 | 110.4 | 2.2 | 2.6 | 2.9 | 3.4 | 4.3 | 5.0 | 5.7 | 6.5 |
100(AU) | 114.1 | 114.5 | 2.3 | 2.7 | 3.0 | 3.5 | 4.5 | 5.2 | 5.9 | 6.7 |
125 | 140.0 | 140.4 | 2.8 | 3.3 | 3.7 | 4.3 | 5.5 | 6.3 | 7.2 | 8.1 |
150 | 160.0 | 159.5 | 3.2 | 3.7 | 4.2 | 4.8 | 6.3 | 7.1 | 8.3 | 9.3 |
Conduit Length Chart
Size of conduit | Comprimento |
Up to size 63 | 4 m + 20, -0 mm |
Above size 63 | 6 m + 50, -0 mm |
Mechanical Properties
The standard outlines stringent mechanical performance requirements to ensure the conduits and fittings can withstand various stresses:
Bending Strength:
The bending test described in AS/NZS 2053.2 evaluates the mechanical flexibility and durability of conduits subjected to bending forces during installation or use. The test ensures that conduits classified for specific mechanical stress levels can withstand bending without visible damage, preserving their functionality and integrity. Here is a summary of the requirements and procedures outlined in the standard:
Applicability
The bending test applies only to certain classifications and sizes of conduits:
Applicable Conduits:
Conduits with diameters less than 32 mm.
Those classified as suitable for:
Very light mechanical stress.
Light mechanical stress.
Medium mechanical stress.
Exempted Conduits:
Conduits with diameters equal to or greater than 32 mm.
Heavy-duty and very heavy-duty conduits, which are not required to undergo this test.
Test Procedure
The bending test involves the following steps:
- Colocação:
Position the 500 mm test piece in the groove of the bending device, securing it lightly with the clamp.
- Bending:
Use the bending rollers to move the test piece around the former, creating a bend of approximately 180°.
After release, the test piece should retain a bend of 90°.
- Removal:
Remove the bending device without causing additional damage to the test piece.
Acceptance Criteria
After completing the test:
- The conduit must exhibit no cracks visible to normal or corrected vision without magnification.
- The conduit’s structural integrity must remain intact to ensure suitability for electrical installations.
Compression Resistance:
The compression resistance test ensures that conduits can withstand compressive forces during installation and operational use without significant deformation or compromising structural integrity. This test evaluates how well a conduit maintains its shape and performance when subjected to specified loads.
Applicability
The test applies to all conduits covered under AS/NZS 2053.2 and references the general compression resistance test outlined in Part 1 of the AS/NZS 2053. For a conduit to pass this test:
- The difference between the initial outside diameter and the diameter measured under applied force must not exceed 10%.
Test Pieces
- The test pieces consist of conduit sections cut to a length of 200 mm.
Test Procedure
The test is conducted in a controlled environment following these steps:
- Measurement and Conditioning:
Measure and record the initial outside diameter of the test piece.
Place the test piece in the conditioning chamber at 20°C ± 1°C for at least 10 hours.
- Compression Force Application:
Apply a compression force uniformly, ensuring it reaches the specified value within 30 ± 3 seconds.
Maintain the force for 60 ± 6 seconds.
- Measurement During Force:
While the force is applied, measure and record the outside diameter of the compressed section of the test piece.
- Post-Compression Measurement:
Remove the force and the intermediate piece.
After 1 minute, measure the outside diameter of the test piece at the point of applied force.
- Calculation:
The difference between the initial diameter and the diameter under applied force.
The difference between the initial diameter and the diameter measured after force removal.
Compression Force Data Sheet
Conduits | Compression force N |
Very light | 125 |
Light | 320 |
Médio | 750 |
Pesado | 1250 |
Very heavy | 4000 |
Acceptance Criteria
A conduit passes the compression resistance test if:
- During Force Application:
The reduction in diameter during the test does not exceed the maximum allowable value specified in the relevant part of the standard.
- Post-Compression Recovery:
After the force is removed, the difference between the initial diameter and the post-test diameter does not exceed 10%.
Resistance to Collapse:
The collapse resistance test evaluates the ability of electrical conduits to maintain their structural integrity under mechanical stress and elevated temperatures. This test is particularly significant for conduits subject to bending during installation or operation in environments with high temperatures. It ensures that conduits retain sufficient internal diameter to protect and accommodate electrical cables effectively.
Applicability
The collapse test applies to conduits classified under AS/NZS 2053.2 with diameters less than 32 mm and designed for:
- Very light mechanical stress
- Light mechanical stress
- Medium mechanical stress
Exemptions:
Conduits with diameters of 32 mm or greater, as well as heavy-duty and very heavy-duty conduits, are not subjected to the collapse test due to their inherently robust design and material properties.
Test Pieces
Test pieces consist of conduit sections prepared according to Table C1 of the standard.
Lengths of Test Pieces in AS/NZS 2053.2
Nominal size | Minimum length of samples mm |
16 | 340 |
20 | 370 |
25 | 450 |
32 | 590 |
40 | 740 |
50 | 900 |
63 | 1130 |
Test Procedure
The procedure for evaluating collapse resistance involves the following steps:
- Bending the Test Piece:
At room temperature, gradually bend the conduit through an angle of 90° using the specified bending device.
The bending radius and method must comply with the relevant requirements in AS/NZS 2053.
- Conditioning:
Transfer the secured test piece to the conditioning chamber.
Maintain the chamber at the maximum installation temperature recommended by the manufacturer (±2°C) for a duration of 24 hours.
- Post-Conditioning Assessment:
Remove the rigid support and the test piece from the conditioning chamber.
Measure the minimum internal diameter of the conduit and ensure it complies with the requirements outlined in the relevant part of the AS/NZS 2053 series.
Acceptance Criteria
A conduit passes the collapse resistance test if:
The specified gauge passes through the minimum internal diameter of the conduit after conditioning, confirming that the internal space remains unobstructed.
Resistance to Heat:
The resistance to heat test evaluates a conduit’s ability to withstand the maximum service temperature specified by the manufacturer without significant deformation. This test ensures that conduits and fittings maintain their structural integrity and protective function under high-temperature conditions, a critical consideration for electrical installations in environments subject to heat exposure.
Test Pieces
The test is performed on three prepared samples:
Each sample is an 80 mm length, halved longitudinally, with one half from each length subjected to testing.
Test Procedure
The resistance to heat test involves the following steps:
- Preparação:
Place the ball-pressure apparatus and the steel support in the heating chamber.
Preheat the chamber to the manufacturer-specified maximum service temperature (±5°C) and ensure the apparatus and support reach this temperature.
- Positioning:
Place the test piece on the steel support within the chamber.
Apply a 20 ±0.2 N force to the test piece using the steel ball for a duration of 60 minutes ±1 minute.
- Resfriamento:
After the test duration, remove the test piece and immerse it in cold water.
Ensure the piece reaches room temperature within 10 seconds.
- Measurement:
Measure the diameter of the impression made by the steel ball on the test piece using precise tools.
Acceptance Criteria
A test piece passes the resistance to heat test if:
The diameter of the impression made by the ball does not exceed 2 mm
Resistance to Burning:
The resistance to burning test ensures that non-metallic and composite conduits and fittings exhibit sufficient resistance to flame propagation. This assessment is crucial for identifying materials that can prevent or limit the spread of fire in electrical installations. Products that pass this test are classified as non-flame propagating, enhancing safety in fire-sensitive environments.
Key Test Overview
This test is conducted using a 1 kW flame in accordance with AS/NZS 4695.2.41 and involves:
- Measuring the ignitability and flame propagation properties of representative samples.
- Evaluating fittings of similar material and design under equivalent conditions.
- Exempting small fittings from testing due to negligible impact on flame behavior.
Apparatus Required
The test setup includes:
- Test Enclosure:
A rectangular metal enclosure with an open face to control environmental variables and minimize draughts.
- Mounting Components:
Metal clamps and steel rods to position conduits and fittings securely.
- Tissue Paper and Pinewood Board:
A layer of white tissue paper (mass of 12–25 g/m²) placed over a pinewood board at the bottom of the enclosure to detect falling molten material.
- 1 kW Burner:
Positioned at a 45 ±2° angle to simulate flame exposure under controlled conditions.
Test Pieces
The test is carried out on three samples:
Conduits:
A 675 ±10 mm length is mounted vertically using two clamps, spaced 550 ±10 mm apart.
Testing Procedure
The test involves the following steps:
- Montagem:
Secure the sample vertically in the enclosure using clamps or suspension.
- Flame Application:
Direct the burner flame at a 45° angle onto the sample for 60 ±1 seconds.
Ensure the flame intersects the surface of the sample at specified points based on the type of test piece.
- Observation:
Monitor flame behavior and any material fallout during the test.
- Post-Test Inspection:
Allow the sample to cool.
Wipe the surface with a water-soaked cloth to remove soot and assess damage.
Acceptance Criteria
A sample passes the resistance to burning test if:
- It does not ignite during flame application.
- Burning or charring is absent within 50 mm of the upper and lower clamps after wiping.
- Combustion ceases within 30 seconds after flame removal.
- Tissue paper at the enclosure’s base remains unignited.
- Molten material present on the sample’s surface does not result in burning or charring.
características elétricas
Insulating: The conduit must offer high electrical insulation to protect cables and prevent accidental contact with conductive elements.
External Influences
Resistência à corrosão: Materials must resist degradation from moisture, chemicals, and soil.
Electromagnetic Compatibility (EMC)
Ensures the conduit does not interfere with or become affected by electromagnetic fields.
AS/NZS 2053.5 – Corrugated Conduits and Fittings
The AS/NZS 2053.5 standard defines the requirements for non-threadable corrugated conduits and their associated fittings made of insulating materials. These conduits are used to protect electrical cables in installations, offering flexibility, mechanical protection, and resistance to external influences. This standard is closely linked to AS/NZS 2053.1, which provides general requirements and guidelines.
Scope and Applicability
This standard applies to:
- Non-threadable corrugated conduits of insulating materials.
- Fittings specifically designed to be used with corrugated conduits.
- Electrical installations requiring cable protection under varying environmental and mechanical conditions.
Classification
Corrugated conduits and fittings are classified based on the following, these are what applicable for AS/NZS 2053.5:
According to mechanical properties:
Light duty
Medium duty
Heavy duty
According to flame propagation:
Non-flame propagating
Electrical Characteristics:
Ability to provide electrical insulation and prevent continuity issues.
Dimensions of corrugated conduits
The standard specifies nominal diameters, wall thicknesses, and tolerances for corrugated conduits.
Mechanical Properties
The following mechanical tests ensure corrugated conduit performance under stress:
Bending Test:
The bending test outlined in AS/NZS 2053.5 ensures that non-threadable corrugated conduits can withstand mechanical stress during installation and use. This test evaluates the conduit’s ability to maintain its structural integrity and functionality when subjected to repetitive bending movements at both standard and low-temperature conditions.
Test Pieces
- Six test pieces are required, each with a length of at least 12 times their outside diameter.
- Three samples are tested at 20°C, while the remaining three are tested at the manufacturer-specified lowest installation temperature.
Test Procedure
- Test at 20°C
(a) Conditioning:
Place the test piece and apparatus in the conditioning chamber for 2 hours at 20°C ±1°C.
(b) Bending Process:
Perform the following sequence by hand:
Bend the test piece 90° to the left.
Return it to the vertical position.
Bend the test piece 90° to the right.
Return it to the vertical position.
Hold the position for 1 minute after each step.
Repeat the sequence 4 times, but on the final cycle, stop at 90° to the right and hold the position for 5 minutes.
(c) Gauge Test:
Rotate the bending apparatus to align the straight sections of the test piece at a 45° angle to the vertical.
Pass the diameter gauge through the conduit under its own weight, ensuring no initial velocity is applied.
- Test at Lowest Installation Temperature
(a) Conditioning:
Place the test piece and apparatus in the conditioning chamber for 2 hours at the manufacturer-specified lowest installation temperature ±2°C.
(b) Repeat Bending Sequence:
Follow the same bending steps and gauge test outlined for 20°C testing.
Criteria for Acceptance
A conduit passes the bending test if:
The gauge passes through the conduit under its own weight without any applied force.
There are no visible cracks on the test piece observed with normal or corrected vision, without magnification.
Compression Resistance:
The Compression Resistance Test as specified in AS/NZS 2053.5 evaluates the ability of corrugated conduits and fittings to resist deformation when subjected to compressive forces. The procedure follows the same methodology outlined for rigid plain conduits in AS/NZS 2053.2, but the acceptance criteria requirement is different.
For corrugated conduits: The difference between the initial outside diameter and the diameter measured under compression does not exceed 25% of the initial diameter.
Collapse Test:
The collapse test procedure of corrugated conduit is the same as rigid plain conduit, which all test according to AS/NZS 2053.1.
And the corrugated conduit passes the collapse resistance test if:
The specified gauge passes through the minimum internal diameter of the conduit after conditioning, confirming that the internal space remains unobstructed.
Flexing Test:
The Flexing Test, as outlined in AS/NZS 2053.5, assesses the durability and mechanical resilience of corrugated conduits and their terminating fittings when subjected to repeated bending movements. This test ensures that the conduits can endure dynamic mechanical stresses encountered during installation or in service without compromising their structural integrity or functionality.
Test Procedure
Montagem:
Fix the test piece to the oscillating member of the apparatus by its terminating fitting.
Align the conduit so that, at the midpoint of its travel, its axis is vertical and passes through the axis of oscillation.
Flexing Motion:
Subject the test piece to 5000 flexings at a rate of 40 flexings per minute.
Each flexing involves a full cycle of movement, starting from the vertical position and moving backwards and forwards through an angle of 180°.
Inspection:
After completing the test, inspect the test piece for structural damage using normal or corrected vision, without magnification.
Acceptance Criteria
There are no visible signs of structural damage upon inspection with normal or corrected vision.
Resistance to Heat:
Test Procedure
Heat Conditioning:
Place the test piece and heat test apparatus in the conditioning chamber.
Maintain the specified highest installation temperature for 4 hours.
Load Application:
Apply a load through a 6 mm steel rod, positioned as perpendicular as possible to the conduit’s axis, as shown in bellow.
Load for Resistance to Heat Test of AS/NZS 2053.5
Conduits | Mass kg |
Light | 1.0 |
Médio | 2.0 |
Pesado | 4.0 |
Resfriamento:
After 24 hours, remove the test piece and apparatus from the chamber and allow them to cool to room temperature.
Gauge Test:
Remove the load and attempt to pass the appropriate gauge through the test piece under its own weight, without any initial velocity, with the conduit in a vertical position.
Acceptance Criteria
The test piece passes if:
The gauge successfully passes through the conduit under its own weight, without any additional force or velocity.
Resistance to Burning:
The burning resistance test of corrugated conduits is same as rigid plain conduit. With same requirements.
Electrical Characteristic
Electrical Continuity: Not applicable
Insulating: Same requirements as rigid plain conduit in AS/NZS 2053.2.
External Influences
Same requirements as rigid plain conduit in AS/NZS 2053.2.
Electromagnetic Compatibility
Same as rigid plain conduits in AS/NZS 2053.2
AS/NZS 2053.6 - Profile-Wall, Smooth-Bore Conduits and Fittings
AS/NZS 2053.6 specifies the requirements for rigid, non-threadable, profile-wall, smooth-bore conduits and fittings made from insulating materials. These conduits are designed for protecting cables in electrical installations and are available in designated sizes ranging from 90 mm to 150 mm.
Definição
Profile-wall, smooth-bore conduits: Conduits with a smooth inner surface for easy cable insertion and a profile wall (which may be hollow) for strength. These conduits are typically not intended for bending.
Classification according to Mechanical Strength:
Light Duty
Dever médio
Trabalho pesado
Dimensions of Conduits
The dimensions of conduits are controlled to ensure compatibility with associated fittings. The specified diameters, socket dimensions and tolerances ensure both mechanical stability and electrical performance.
Mechanical Properties
AS/NZS 3053.6 lists the mechanical strength requirements for the Profile-wall, smooth-bore conduits and fittings, details as follows:
Compression Resistance:
The conduits compression test and requirements are similar as rigid plain conduits and corrugated conduits, all tested according to AS/NZS 2053.1. But for profile-wall, smooth-bore conduits, the difference between the initial outside diameter and the diameter measured with the force still applied should not exceed 25%.
The other mechanical strength test for profile-wall, smooth-bore conduits are not applicable, such as: bending, collapse, impact, pull-out strength of joints tests.
Resistance to Heat
The conduits are tested to ensure structural stability at the highest installation temperature specified by the manufacturer. Testing includes exposure to the designated temperature for 4 hours under specified load conditions:
Procedure:
- Place the test piece and apparatus in the conditioning chamber.
- Maintain the chamber at the highest installation temperature (±2°C) for 4 hours.
- Apply the load using a 6 mm steel rod as specified in Table AA1.
- After 24 hours, remove the test piece and allow it to cool to room temperature.
- Test if the gauge passes through the conduit under its own weight.
Acceptance Criterion:
The conduit passes if the gauge moves freely through without resistance.
Resistance to Burning
The materials must exhibit flame retardant properties. Tests ensure that the conduit resists ignition and self-extinguishes after removal of the flame source. Flammability ratings are determined in accordance with AS/NZS 2053.1, same like rigid plain conduits and corrugated conduits.
características elétricas
Electrical Continuity: Not applicable
Insulating: Same as rigid plain conduits and corrugated conduits
External Influences
Same as rigid plain conduits and corrugated conduits except that, Conduits and fittings of insulating material are classified as having high protection (inside and outside) against corrosive and polluting substances and need not be tested.
Electromagnetic Compatibility
Same as rigid plain conduits and corrugated conduits
Case Study
At Ledes, our commitment to excellence is reflected in every step of the production process for our Australian Standard rigid conduits and corrugated conduits. By aligning with the stringent requirements of standards like AS/NZS 2053.2 and AS/NZS 2053.5, we ensure that our products consistently deliver superior performance, durability, and safety across diverse applications.
Ledes AS/NZS 2053 Certified Electrical Conduit & Fittings
Our product portfolio includes:
Heavy-Duty Rigid Conduits: Built for high mechanical stress environments, offering superior compression and impact resistance.
Medium-Duty Rigid Conduits: Lightweight yet durable solutions for less demanding applications.
Medium-Duty Communication Rigid Conduits: Lightweight and suitable for communication systems.
Heavy-Duty Corrugated Conduits: Flexible, strong, and capable of withstanding harsh environmental conditions.
Medium-Duty Corrugated Conduits: Ideal for dynamic applications requiring easier handling and installation.
Medium-Duty Communication Corrugated Conduits: For communication applications.
Acessórios: Engineered to ensure secure and reliable connections, including bends, couplings, adaptors, and junction boxes etc.
Advantages of Ledes Australian Standard Conduits and Fittings
All Ledes conduits and fittings are manufactured to align with AS/NZS 2053 standards, offering key benefits such as:
Mechanical Strength: Excellent resistance to compression, impact, and deformation under load, ensuring durability in both underground and exposed installations.
Thermal Performance: Stability at high installation temperatures, maintaining structural integrity even under prolonged exposure to heat.
Flame Retardancy: Rigid and corrugated conduits meet flame-resistance requirements, with options for Low Smoke Halogen-Free (LSZH) materials that reduce toxic emissions during a fire.
Facilidade de instalação: Smooth bore for easy cable pulling and profile-wall construction for enhanced strength.
Environmental Resistance: High resistance to UV exposure, moisture, and corrosive substances, making them ideal for outdoor and industrial applications.
Quality Control at Ledes
At Ledes, we believe that superior products begin with strict quality control measures at every stage:
1. Raw Material Selection:
- Only premium-grade PVC and insulating materials are used to ensure compliance with mechanical, thermal, and electrical performance standards.
- Raw materials undergo thorough testing for purity, composition, and consistency.
- Low Smoke Halogen-Free (LSZH) Options: To cater to projects with heightened safety demands, such as subway systems, we also offer LSZH conduits and fittings that minimize smoke and toxic gas emissions during fires.
2. Precision Manufacturing:
At Ledes, precision manufacturing is the cornerstone of our ability to produce high-performance Australian Standard conduits and fittings. Our state-of-the-art production process ensures each product meets the rigorous demands of AS/NZS 2053 standards. Key highlights of our manufacturing process include:
- Advanced Extrusion Technology
Precision Extrusion:
Using cutting-edge extrusion machines, we produce rigid and corrugated conduits with consistent wall thickness, dimensional accuracy, and a smooth internal bore.
This precision ensures seamless cable pulling and eliminates risks of cable abrasion during installation.
Profile-Wall Construction:
For corrugated conduits, our extrusion process incorporates a reinforced profile-wall structure. This combines flexibility with high mechanical strength, making the conduits suitable for dynamic environments and tight installation spaces.
Controlled Cooling Systems:
After extrusion, conduits pass through controlled cooling tanks to solidify their structure without internal stress, ensuring long-term durability and resistance to environmental factors.
Automated Fitting Production
Injection Molding for Fittings:
Our fittings, including couplings, adaptors, and junction boxes, are manufactured using high-precision injection molding machines.
This process guarantees tight tolerances, smooth edges, and secure fitment, ensuring compatibility with all Ledes conduits and compliance with AS/NZS standards.
- Real-Time Monitoring and Adjustments
Computerized Monitoring Systems:
Throughout the production process, real-time monitoring systems control variables like temperature, pressure, and extrusion speed to ensure uniform quality across all batches.
Any deviations are flagged immediately, and adjustments are made to maintain precision.
Batch Coding and Traceability:
Each batch of product is coded for traceability, enabling thorough quality assurance and ensuring that every product delivered to our clients meets strict specifications.
- Post-Manufacturing Finishing
Cutting and Chamfering:
Conduits are precision-cut to ensure clean ends and uniform lengths, facilitating easier installation. For rigid conduits, chamfering is applied to the ends for a snug fit with fittings.
End-Bell Formation:
For rigid conduits, end-bell formations are produced during the extrusion process to ensure quick and secure connections without additional accessories.
Custom Lengths and Packaging:
We offer customizable lengths and professional packaging to meet project-specific requirements, reducing waste and installation time for contractors.
3. Rigorous Testing:
We select samples from every production batch for testing, replicating the procedures outlined in AS/NZS 2053. These tests include:
Compression resistance
Collapse test
Heat resistance
Flame retardancy
The Melbourne Tunnel Project: A Success Story
The Melbourne Tunnel Project is a landmark infrastructure initiative aimed at enhancing Melbourne’s urban transit system by delivering a world-class underground rail network. Designed to alleviate congestion and improve connectivity, the project involves constructing twin 9-kilometer tunnels, state-of-the-art stations, and advanced systems to support high-capacity rail services. With stringent safety and environmental standards, the project represents a monumental leap in Australia’s commitment to sustainable and efficient public transport.
Ledes’ Conduits and Fittings in the Project
Ledes proudly supplied Australian Standard rigid conduits, corrugated conduits, and fittings for the Melbourne Tunnel Project. These components played a pivotal role in ensuring the safety, reliability, and efficiency of the electrical installations within this critical infrastructure.
The key products selected for this project are Ledes’ Low smoke halogen free conduits and fittings, due to excellent fire resistance, low toxicity, and durability, they play a crucial role in the project to ensure meet stringent requirements for electrical safety, reliability, and environmental performance.
The conduits were instrumental in protecting critical cabling systems from mechanical damage, external influences, and fire risks, making them an essential component of this ambitious project.
How to Choose the Right Electrical Conduit Supplier?
There are 8 pro tips for choosing the right PVC conduit supplier in Australia and New Zealand,
- Compliance with Standards: Ensure the supplier’s products meet Australian Standards (e.g., AS/NZS 2053, IEC 61386) and local building codes.
- Certification and Testing: Verify that the supplier provides certifications and test reports proving compliance with regulatory requirements.
- Proven Project Experience: Look for suppliers with a track record in major local infrastructure projects, demonstrating reliability and adherence to standards.
- Garantia da Qualidade: Evaluate their quality control processes, including raw material sourcing, production monitoring, and batch testing for consistent product quality.
- Linha de produtos: Choose a supplier with a comprehensive product portfolio, including rigid and corrugated conduits, low-smoke halogen-free options, and various fittings.
- Technical Support: Consider suppliers that offer technical guidance, installation support, and customized solutions to meet project-specific needs.
- Timely Delivery: Prioritize suppliers with a reliable distribution network and the ability to meet project deadlines.
- Price vs. Value: While price is important, focus on overall value, including product durability, compliance, and reliability. A slightly higher upfront cost may save on replacements and maintenance in the long run.
Conclusão
The AS/NZS 2053 series establishes a comprehensive framework for electrical conduit systems, ensuring safety, performance, and compliance with Australian and New Zealand standards. By understanding the requirements of these standards and choosing products that meet their rigorous criteria, you can achieve reliable and high-quality installations.